Input parameters | Name | Idex  | Remarks  |  Rated voltage  | Three phase 380V/400V (can be customized for any voltage) Single phase 220V/230V (can be customized for any voltage)  | Three phase three wire (L1, L2, L3) + ground wire (PE) Single phase two line (L, N) + ground line (PE)  |  Input voltage range
   | ±15%(other ranges can be customized)  |    |  Input frequency
   | 40-70HZ  |    |  
 
 
 Output parameters | Name | Idex  | Remarks  |  Modulation mode  | IGBT/SPWM  |    |  Output voltage  | Three phase 0-520V adjustable, single-phase 0-300V adjustable (customizable higher voltage)  |    |  Output voltage stability (average)  | ±1%(Customizable higher precision)  |    |  Reaction time  | 2mS(For input voltage)  |    |  Voltage waveform distortion THD  | < 2%(Linear load)  |    |  Output frequency  | 41Hz-73Hz adjustable,50/60/400Hz fixed(optional100Hz/200Hz,5-1000Hz can be customized)  |    |  Frequency stability  | < 0.1%  |    |  Phase shift  | When the load is three phase equilibrium or no load, it is ≤±1°; the 100% three-phase imbalance is ≤±4°  |    |  Three phase imbalances  | Automatic balance of three-phase voltage  |    |  isolation transformer  | △/Y  |    |  
 
 Control parameters
 | Name | Idex  | Remarks  |  Main control element  | The main measurement and control chip is ARM32 bit processor, and the inverter is IGBT.  |    |  Carrier frequency  | 4K;8K;12K;16K optional
   |    |  Control voltage and current acquisition mode  | Value of validity  |    |  control mode  | Voltage closed loop control or current closed loop control or VF curve control.  |    |  Interface  | RS232,MODBUS-RTU protocal
   | optional TCP/IP,GPRS  |  
 
 
 Display parameters | Name | Idex  | Remarks  |  Display medium  | 7 inch touch screen or 192*64(LCD)  |    |  Display rated parameters  | Input three-phase voltage and frequency;
  Output three phase line voltage and frequency;
  The average value of output line voltage;
  Output power factor;
  Output three-phase current;
  Output active power, apparent power  |    |  Display alarm content  | Fuse break, high IGBT temperature, high transformer temperature, IGBT fault, overload, undervoltage and so on.  |    |  Rated parameter display precision  | 1.0 grade  |    |  Voltage parameter resolution  | 0.1V  | Customizable higher resolution  |  Current parameter resolution  | 0.1A  | Customizable higher resolution  |  
 
 
 Protection parameters | Name | Idex  | Remarks  |  Type of protection  | nput no fuse switch, output no fuse switch, electronic circuit fast detection over current, overvoltage, overload, high temperature, short circuit and automatic jump off protection and alarm  |    |  Protection mode  | Cut off the output  |    |  
 
 
 Physical parameters | Name | Idex  | Remarks  |  Cooling mode  | Natural cooling or forced air cooling or water cooling  |    |  Protection grade  | Indoor IP21; outdoor IP33 or higher level  |  |  
     
											        
											        
											      
											 | 
        								 
    								 
								 | 
            				 
          				 
      				   |